AL20SA - Germany

CodeOld CodeAreaNo of WiresDiameter WireDiameter Cond.Mass per unit lengthRated StrengthDC resistance Calculated using aluminum and steelDC resistance Calculated using aluminum onlyFinal Modulus of elasticityCoefficient of linear expansionCurrent carrying capacity
mm2mmmmkg/kmkNW / kmW / kmN/mm21/kA
24-A20SA2534.272.16.3161.532.493.536 44.699 5159 0001.30E-0565
34-A20SA3534.472.57.522946.042.495 33.316 0159 0001.30E-0580
49-A20SA5049.5739329.766.31.732 82.302 8159 0001.30E-05115
66-A20SA7065.8192.110.544188.181.310 21.741 2159 0001.30E-05135
93-A20SA9593.3192.512.5624.9124.980.924 51.228 6159 0001.30E-05170
117-A20SA120117192.814783.9156.770.737 00.979 4159 0001.30E-05195
147-A20SA150147.1372.2515.8989.2197.130.588 10.781 5159 0001.30E-05225
182-A20SA185181.6372.517.51 221.2243.380.476 40.633 1159 0001.30E-05255
243-A20SA240242.5612.2520.31 636.13250.357 90.475 6157 0001.30E-05310
299-A20SA300299.4612.522.52 019.8401.240.289 90.385 2157 0001.30E-05355
Direction of lay of external layer is right hand(Z)
values of final modulus of elasticity and coefficient of linear expansion for the conductor sizes listed in the Table are used in Germany
Values for other conductor constructions may be calculated using the method given in IEC 61597
Guideline values of current carrying capacity are valid up to a frequancy of 60 Hz, assuming a wind velocity of 0.6 m/s, the effect of solar radiation for Germany, an initial ambient temperature of 35C and a conductor temperature of 80C. For special applications, when there is no air turbulence, the values should be reduced by 30%