AL3/ST1A - Germany

CodeOld CodeArea AIArea SteelArea Total mm2No of Wires ALNo of Wires SteelDiameter Wire AI mmDiameter Wire Steel mmDiameter Core. mmDiamere Cond. mmMass per unit length kg/kmRated Strength kNDC resistance Ω / kmFinal Modulus of elasticity N/mm2Coefficient of linear expansion 1/kCurrent carrying capacity A
15-AL3/3-ST1A16/2.515.32.5417.8611.81.81.85.461.67.482.160 281 0001.92E-05100
24-AL3/4-ST1A23.93.9827.8612.252.252.256.7596.211.691.382 581 0001.92E-05135
34-AL3/6-ST1A35/634.45.7340.1612.72.72.78.1138.616.660.960 181 0001.92E-05165
44-AL3/32-ST1A44/324431.775.614722.47.211.2369.149.080.756 6110 0001.50E-05
48-AL3/8-ST1A50/848.38.0156.3613.23.23.29.6194.723.080.683 581 0001.92E-05200
51-AL3/30-ST1A50/3051.229.8811272.332.336.9911.7374.649.120.649 6107 0001.53E-05
70-AL3/11-ST1A70/1269.911.481.32671.751.444.3211.728233.960.475 677 0001.89E-05270
94-AL3/15-ST1A95/1594.415.3109.72672.151.675.0113.6380.345.790.352 177 0001.89E-05330
97-AL3/56-ST1A95/5596.556.3152.81273.23.29.616706.590.40.344 4107 0001.53E-05
106-AL3/76-ST1A105/75105.775.5181.214193.12.2511.317.5885119.560.315 5110 0001.50E-05
122-AL3/20-ST1A120/20121.619.8141.42672.441.95.715.5490.659.090.273 477 0001.89E-05385
122-AL3/71-ST1A120/70122.171.3193.41273.63.610.818894.2114.410.272 1107 0001.53E-05
128-AL3/30-ST1A125/30127.929.8157.83072.332.336.9916.3586.671.760.260 182 0001.78E-05400
149-AL3/24-ST1A150/25148.924.2173.12672.72.16.317.1600.372.280.223 377 0001.89E-05445
172-AL3/40-ST1A170/40171.840.1211.83072.72.78.118.9787.796.360.193 782 0001.78E-05490
184-AL3/30-ST1A185/30183.829.8213.626732.336.991974.488.240.180 977 0001.89E-05505
209-AL3/34-ST1A210/35209.134.1243.22673.22.497.4720.3843.5100.540.159 077 0001.89E-05555
212-AL3/49-ST1A210/50212.149.5261.530733921972.5118.960.156 982 0001.78E-05575
231-AL3/30-ST1A230/30230.929.8260.82473.52.336.9921870.1102.140.143 974 0001.96E-05595
243-AL3/39-ST1A240/40243.139.5282.52673.452.688.0421.8979.4116.720.136 877 0001.89E-05605
264-AL3/34-ST1A265/35263.734.1297.72473.742.497.4722.4993.6116.640.126 074 0001.96E-05640
304-AL3/34-ST1A300/50304.349.5353.72673.863924.41 226.4146.160.109 277 0001.89E-05700
305-AL3/39-ST1A305/40304.639.5344.15472.862.688.0424.11 150.3134.880.109 370 0001.93E-05700
339-AL3/30-ST1A340/30339.329.8369.148732.336.99251 170.2134.120.098 062 0002.05E-05740
382-AL3/49-ST1A380/50381.749.5431.2547339271 441.4169.010.087 270 0001.93E-05790
386-AL3/34-ST1A385/3538634.1420.14873.22.497.4726.71 332.4152.740.086 262 0002.05E-05800
434-AL3/56-ST1A435/55434.356.3490.65473.23.29.628.81 640.0190.040.076 670 0001.93E-05845
449-AL3/39-ST1A450/40448.739.5488.24873.452.688.0428.71 547.7177.390.074 162 0002.05E-05865
490-AL3/64-ST1A490/65490.363.6553.85473.43.410.230.61 851.4214.540.067 970 0001.93E+05905
550-AL3/71-ST1A550/70549.771.3620.95473.63.610.832.42 075.6240.520.060 570 0001.93E+05960
562-AL3/49-ST1A560/50561.749.5611.24873.863932.21 937.8222.110.059 262 0002.05E-05980
679-AL3/86-ST1A680/85678.686764.5541942.412362 547.6298.170.049 068 0001.94E-0501 08
NOTE1 Direction of lay of external layer is right hand(Z)
NOTE2 values of final modulus of elasticity and coefficient of linear expansion for the conductor sizes listed in the Table are used in Germany
Values for other conductor constructions may be calculated using the method given in IEC 61597
NOTE3 Guideline values of current carrying capacity are valid up to a frequancy of 60 Hz, assuming a wind velocity of 0.6 m/s, the effect of solar radiation for Germany, an initial ambient temperature of 35C and a conductor temperature of 80C. For special applications, when there is no air turbulence, the values should be reduced by 30%